ANTSPACE HK3
Plate Heat Exchanger Specifications 1Set 1030KW 210 Rack Space
Description
Specifications
Specification Details For ANTSPACE HK3
Product Overview | Value |
Version | ANTSPACE HK3 |
Dimensions (l*w*h), mm | 6058*2438*2896 |
Miner capacity | 210 units -S19 Hyd. & S21 Hyd. Series miner |
Container certification | China Classification Society Certification |
Safety certification | North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21, CSA C22.2 No. 14-18,ANSI/ISO 12100:2012 EU/Standards: EN ISO 12100, EN 60204-1 |
Operating power, kW | 1047~1050 |
PUE(Power usage effectiveness) | 1.022 (Excluding cooling tower)/1.036 (Including cooling tower) |
Input voltage and frequency | 415V±5% 60Hz (North America) 400V±5% 50Hz (EU、Middle East) |
Detailed Characteristics | Value |
Shipping weight, T | 8 |
Operating weight, T | 12 |
Main switch of power distribution cabinets, A | 1200(North America) 1250(EU、Middle East) |
Rated current, A | 952 |
Standard power, kW | 1049 |
Maximum power, kW | 1050 |
Rated current per Miner, A | 10 |
Inlet cable | The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase: L1 single core cable 600kcMil(300mm²)x4 L2 single core cable 600kcMil(300mm²)x4 L3 single core cable 600kcMil(300mm²)x4 N Single-core cable 600kcMil(300mm²)x4 PE single-core cable 500kcMil(240mm²)x2 |
Connection interface (Cooling tower) | DN125(GB/T 9119-2010 PN16 DN125) |
Connection interface (Plate heat exchange interface) | DN100(GB/T 9119-2010 PN16 DN100) |
Flow rate, m³/h | >85 |
Quantity of ANTSPACE powered by one 2500kVA Transformer | 2 |
Specification Details For Plate Heat Exchanger
Product Overview | Value |
Type | Plate Heat Exchanger |
Dimensions(L*W*H), mm | 775*480*1069 |
Material | TI |
Detailed Characteristics | Value |
Shipping Weight, kg | 379 |
Operating Weight, kg | 461 |
Connection Interface | DN100(GB/T 9122-2010 PN16 DN100) |
External circulation supply liquid temperature, ℃ | 0~30 |
External circulation flow rate, m³/h | 33~110 |
Internal circulation flow rate, m³/h | 100 |
| Points For Attention
1 | Cooling tower is required to be placed on flat ground, horizontal degree (±1 degree). |
2 | The ground surfaced is required to be hardened and stable, able to withstand at least 14-ton load. |
3 | A 10-ton crane is needed for unloading ANTSPACE and cooling tower. |
4 | Add-on items such as stairs, transformers, cables, bridge racks and cable distribution boxes are not included in the delivery of ANTSPACE. BYTMAINGPX team can provide design suggestions if needed. |
5 | Client needs to confirm the opening direction of container and it needs to face air-intake. Door on left is current design by default. |
6 | Keep at least 2 meters of air in-take space around the cooling tower. |
7 | Altitude: ≤3000m. If the altitude is higher than 1000-meter, transformer and switch should be derated, the total power of ANTSPACE must be decreased by 1% for each elevation increment of 100 meters. |
8 | Operating temperature: -25°C to 40°C. Operating humidity: 10%RH to 90%RH. When the initial coolant temperature is below 20 °C, the internal circulation should be turned on to heat up the coolant to above 20 °C before starting the mining machine. |
9 | When the ambient temperature is below 5 ℃, the cooling tower can be switched to cold-dry mode. |
10 | Choose pure water or suitable antifreeze as coolant based on local climate conditions. |
11 | The suitable ambient temperature for ANTSPACE does not represent the suitable ambient temperature for mining machine. |
| Purchasing Guidelines
1. The ANTSPACE HK3 is recommended to be used simultaneously with The ANTMINER S19 XP Hyd. / ANTMINER S21 Hyd.
2. The pictures shown are for reference only; the final shipment version shall prevail.